본문 바로가기
[학술대회자료]

  • 학술대회자료

정민지(가천대학교) 윤홍익(가교테크) 홍진관(가천대학교)

표지

북마크 0

리뷰 0

이용수 57

피인용수 0

초록

This study investigates the influence of ventilation type on the transport characteristics of coughing particles in Airborne Infection Isolation Room (AIIR), which is commonly called negative pressure isolation room. Computational Fluid Dynamics (CFD) was used to simulate the airflow and for tracing the behavior of particles. The results show that the airflow pattern has a significant influence on the particle dispersion characteristics. Sidewall exhaust system is more effective than ceiling exhaust system for particle removal. Although it is an isolation room that produces unidirectional flow, coughing particles can spread to the whole room and a large number of particles can be deposited onto patient, bed, side rails, healthcare worker, ceiling, floor, and sidewall.

목차

Abstract
1. 연구 배경 및 목적
2. 연구 방법
3. 해석 결과
4. 결론
References

참고문헌(0)