A Novel Detection Algorithm for Instantaneous Voltage Sag Corrector Using Series Compensator A Novel Detection Algorithm for Instantaneous Voltage Sag Corrector Using Series Compensator
A Novel Detection Algorithm for Instantaneous Voltage Sag Corrector Using Series Compensator
초록·키워드
This paper proposes a novel detection algorithm of faulted voltages under the unbalanced condition. To quantify the standard of unbalance under the faulted conditions, the 3-phase unbalanced voltages are decomposed into two balanced 3-phase symmefrical components of the positive and negative sequence voltages, which is defined by the magnitude factor (MF) and unbalance factor {UF). It is analyzed that MF and UF values are given as the dc constant values even though unbalance condition. This paper also proposes the control scheme of the instantaneous voltage sag corrector based on this detection algorithm. The validity of the proposed algorithm is verified through the EMTDC simulation and experiments.