Numerical Analysis of Axial-Flow Cyclone Separator for Subway Station HVAC System Pre-Filter
논문 기본 정보
- 저자정보
- 저널정보
- 대한설비공학회 International Journal of Air-Conditioning and Refrigeration International Journal of Air-Conditioning and Refrigeration Vol.17 No.3
- 발행연도
- 2009.9
- 수록면
- 94 - 99 (6page)
Numerical Analysis of Axial-Flow Cyclone Separator for Subway Station HVAC System Pre-Filter
초록·키워드
In the Korean subway station, three types of pre-filters, which include auto filter, electrostatic precipitator (ESP) and auto cleaning demister, are widely used. However, these devices have some problems such as the difficulty of maintenance and high operating cost. In this study, axial-flow cyclone separator was employed as a pre-filter inside a heating, ventilation, and air conditioning (HVAC) system. 3-dimensional computational fluid dynamics (CFD) analysis was performed on a single unit axial-flow cyclone and coupled unit axial-flow cyclone. Calculated and measured pressure drop of the designed axial-flow cyclone were found be comparable to other types of pre-filters and the observed cut-off diameter was less than 10 micron. Considering lower operating and maintenance cost, axial-flow cyclone was proved to be a better solution as a pre-filter.
본문·목차
인공지능 문자 인식 모델을 통해 추출된 텍스트로, 일부 오타나 오류가 포함될 수 있으나 지속적으로 개선 중입니다.
오류를 발견하셨다면 해당 부분을 드래그한 후 ' 를 통해 신고해주세요.
오류를 발견하셨다면 해당 부분을 드래그한 후 ' 를 통해 신고해주세요.
최근 본 자료 전체보기
UCI(KEPA) : I410-ECN-0101-2009-553-018852549