HEATING PERFORMANCE OF A GROUND SOURCE HEAT PUMP SYSTEM WITH A SINGLE U-TUBE AND A DOUBLE TUBE TYPE GLHXS

논문 기본 정보

저자정보
(Hanbat National University) (Hanbat National University)
저널정보
한국신재생에너지학회 AFORE AFORE 2011
발행연도
수록면
289 - 289 (1page)
오류 신고하기

피인용 0

HEATING PERFORMANCE OF A GROUND SOURCE HEAT PUMP SYSTEM WITH A SINGLE U-TUBE AND A DOUBLE TUBE TYPE GLHXS
검색

    초록·키워드

    In this study, the performance of ground source heat pump systems with a vertical single u-tube and a vertical double tube type ground loop heat exchangers (GLHXs) was investigated. Both the GLHXs were designed using the GLHEPRO being a very popular commercial program to design various GLHXs [1]. Each heat pump unit for the u-tube and the double tube type GLHX, respectively, had the same capacity by 20 HP. The former and the latter systems had 5 boreholes of 150 m in depth and 3 boreholes of 100 m in depth, respectively. Both the systems were installed in the same school building, but each system was in charge of different spaces for air-conditioning. As shown in Fig. 1, two systems were similar in performanc ... 전체 초록 보기