메뉴 건너뛰기

An Application of Optimum Heat Exchanger for the Grasp on Performance Characteristics of NH₃ Refrigeration System

오류 신고하기

피인용 0

An Application of Optimum Heat Exchanger for the Grasp on Performance Characteristics of NH₃ Refrigeration System
검색

    초록·키워드

    Since the use of CFC and HCFC refrigerants is to be restricted due to the depletion of ozone layer, this experiment applies the NH3 gas to study the performance characteristics from the superheat control for improving the energy efficiency. The experiments are carried out for the condensing pressure of refrigeration system from 1500㎪ to 1600㎪ by 50㎪ and for degree of superheat from 0℃ to 10℃ by 1℃ at each condensing pressure. As a result of experiment, 1) As degree of superheat increased, evaporating pressure of the compressor decreased so equilibrium temperature decreased. And specific volume of refrigerant vapors increased so refrigerant mass flow and heat load of the evaporator decreased. 2) An influence of change of condensing pressure on heat load of the evaporator was insignificant. 3) With the identical degree of superheat, change of compressed temperature was insignificant according to each condensing pressure, so there was little change in enthalpy. 4) when the degree of superheat is 0℃ at each condensing pressure, the refrigeration system has the highest performance.

    최근 본 자료 전체보기

      UCI(KEPA) : I410-ECN-0101-2009-552-016146712