가공송전선 지락시 고장전류의 접지분류계수 산정에 관한 연구 A Study on Calculation of Line-To-Ground Fault Current Split Factor to Earth in Overhead Transmission Lines

논문 기본 정보

저자정보
(한국전력공사) (한국전력공사) (한국전력공사) (한국전력공사) (한국전력공사)
저널정보
대한전기학회 전기학회논문지 전기학회논문지 제57권 제11호
발행연도
수록면
1,929 - 1,932 (4page)
오류 신고하기

피인용 0

가공송전선 지락시 고장전류의 접지분류계수 산정에 관한 연구
검색

    초록·키워드

    In case of a line-to-ground fault at transmission lines, a portion of fault current will flow into the earth through the footings of the faulted tower causing electrical potential rise nearby the faulted tower footings. In this situation, any buried pipelines or structures nearby the faulted tower can be exposed to the electrical stress by earth potential rise. Although many research works has been conducted on this phenomena, there has been no clear answer of the required separation distance between tower footings and neary buried pipeline because of its dependancy on the soil electrical charactersics of the concerned area and the faulted system.