메뉴 건너뛰기

열회수형환기장치의 성능 현황 및 평가방법에 관한 연구 A Study on Performance Status and Test Standard of Heat Recovery Ventilator

논문 기본 정보

저자정보
(한밭대학교) (한밭대학교) (국제기후환경센터)
저널정보
대한설비공학회 설비공학논문집 설비공학논문집 제34권 제3호
발행연도
수록면
145 - 153 (9page)
DOI
10.6110/KJACR.2022.34.3.145
오류 신고하기

피인용 5

열회수형환기장치의 성능 현황 및 평가방법에 관한 연구
검색

    초록·키워드

    Heat recovery ventilators (HRV) are among the major technologies for energy saving and improved indoor air quality. This paper investigated the performance and evaluation standard of HRV. Public data were used for the HRV performance analysis of HRV. The performance distribution (n=788) according to the air volume of the certified HRV was investigated and analyzed In addition, the performance distribution (n=171) by air volume after applying an air filter to reduce fine dust was investigated. The average total heat exchange efficiency for cooling was 54.2% in group 1 and 59.7% in group 2. The average total heat exchange efficiency during heating was 73.4% in group 1 and 74.3% in group 2. It was confirmed that they existed at a similar level without significant change.

    최근 본 자료 전체보기