메뉴 건너뛰기
소속 기관 / 학교 인증
인증하면 논문, 학술자료 등을  무료로 열람할 수 있어요.
한국대학교, 누리자동차, 시립도서관 등 나의 기관을 확인해보세요
(국내 대학 90% 이상 구독 중)
고객센터 ENG
주제분류

논문 기본 정보

저자정보
(Daegu Catholic University) (Korea Electric Power Corporation) (Korea Electric Power Corporation) (Daegu Catholic University)
저널정보
대한전기학회 전기학회논문지 전기학회논문지 제74권 제5호
오류 신고하기

피인용 0

검색

    초록·키워드

    This paper explores the development and implementation of an Energy Storage System (ESS) as a Non-Transmission Alternative (NTA) to address line overload and stability challenges in the Jeju power grid. The primary goal is to enhance grid reliability and efficiency without necessitating extensive expansion of transmission infrastructure, leveraging a 50MW ESS installed at the Geumak substation. The ESS NTA operating system is designed with three distinct operational modes: Mode 1 focuses on mitigating line overload, Mode 2 aims to control line utilization, and Mode 3 is based on renewable energy index-driven control. Each mode incorporates specific algorithms and control strategies, including calculations, control flow diagrams, and program development. Simulation and real-time application results validate the proposed system's effectiveness in reducing line overload, optimizing line utilization, and facilitating the integration of renewable energy.

    최근 본 자료 전체보기

      UCI(KEPA) : I410-151-25-02-093114123