초록·키워드
In industrial processes that recover waste heat for energy reuse, the heat source is often polluted air. When the surface temperature drops below the dew point, condensate can form during the heat recovery process. Pillow-plate heat exchangers are advantageous due to their high resistance to fouling, easy maintenance, and excellent heat transfer performance, as they facilitate heat exchange between two fluids through a single plate rather than an extended surface. Their straightforward design also promotes efficient condensate drainage. Despite numerous experimental studies on pillow-plate heat exchangers, research evaluating their performance in hot and humid conditions is still scarce. This study presents an experimental setup designed to assess the performance of a pillow-plate heat exchanger under such conditions, analyzing heat transfer performance across various operating scenarios. When varying the parameters on the water side, the heat transfer rate changed by approximately 10–20%. In contrast, altering the parameters on the air side resulted in changes of about 25–60%. Overall, it was found that the influence of air-side parameters was approximately 28.2% greater within the tested range. Notably, the heat transfer rate showed significant sensitivity to changes in parameters that affect the absolute humidity of the air.
본문·목차
인공지능 문자 인식 모델을 통해 추출된 텍스트로, 일부 오타나 오류가 포함될 수 있으나 지속적으로 개선 중입니다.
오류를 발견하셨다면 해당 부분을 드래그한 후 ' 를 통해 신고해주세요.
오류를 발견하셨다면 해당 부분을 드래그한 후 ' 를 통해 신고해주세요.
최근 본 자료 전체보기
UCI(KEPA) : I410-151-26-02-094379614