메뉴 건너뛰기
소속 기관 / 학교 인증
인증하면 논문, 학술자료 등을  무료로 열람할 수 있어요.
한국대학교, 누리자동차, 시립도서관 등 나의 기관을 확인해보세요
(국내 대학 90% 이상 구독 중)
고객센터 ENG
주제분류

논문 기본 정보

저자정보
(Soongsil University) (Soongsil University) (Soongsil University) (Soongsil University)
저널정보
대한전기학회 전기학회논문지 전기학회논문지 제75권 제2호
오류 신고하기

피인용 0

검색

    초록·키워드

    As renewable energy sources are increasingly integrated into power systems to mitigate the climate crisis, the adoption of smart inverters—key devices for enhancing the stability of distributed generators like photovoltaic (PV) systems—is being encouraged. Consequently, research on the impact of smart inverters on potential power system fluctuations is also growing. In this paper, a simulated distribution system was constructed to model load power variations and undervoltage conditions caused by single-line-to-ground faults. By configuring various Volt-VAR curves for the smart inverter, its effects on voltage recovery and line loss in the distribution system were analyzed. Our findings confirmed that a smaller slope in the Volt-VAR curve provided a more significant compensation effect for overall voltage drops in the distribution system. Also, setting an excessively large slope could lead to voltage oscillation due to reactive power output, thereby negatively impacting the entire system's stability. Two causes for oscillation phenomena in smart inverters were identified, stemming from their computation and control methods. Despite these inherent operational characteristics, experimental results further confirmed that mitigating these oscillations was achievable by adjusting the slope of the Volt-VAR curve to a gentler setting.