    It cannot always be said that applying varlable speed drives to parallel operation fans are the best choice or the most cost-effective. Depending on the conditions of operating and drive capacity, the vane - speed control will be more favorable than others. In this case, there are lots of combination operating points between the vane opening and the fan speed. The efficiency optimal operating point for a vane - speed parallel fan system is calculated and tested to the forced draft fans in a power plant boiler The results ascertain the validity of the theoretical analysis.