메뉴 건너뛰기

Nonlinear State Feedback for Minimum Phase in Nuclear Steam Generator Level Dynamics Nonlinear State Feedback for Minimum Phase in Nuclear Steam Generator Level Dynamics

오류 신고하기

피인용 0

Nonlinear State Feedback for Minimum Phase in Nuclear Steam Generator Level Dynamics
검색

    초록·키워드

    The steam generator level is susceptible to the nonminimum phase in dynamics due to the thermal reverse effects known as "shrink and swell" in a pressurized water reactor. A state feedback assisted control concept is presented for the change of dynamic performance to the minimum phase. The concept incorporates a nonlinear digital observer as a part of the control system. The observer is deviced to estimate the state variables that provide the true indication of water inventory by compensating for shrink and swell effects. The concept is validated with implementation into the steam generator simulation model.

    최근 본 자료 전체보기

      UCI(KEPA) : I410-ECN-0101-2009-569-017764482