메뉴 건너뛰기

지하철 역사 지하수를 이용한 에어와셔에 관한 연구 Study on Air Washer using Underground Water in the Subway Stations

논문 기본 정보

저자정보
(부경대학교) (GE엔지니어링) (부경대학교) (동명대학교) (부경대학교)
저널정보
한국수산해양교육학회 수산해양교육연구 수산해양교육연구 제22권 제4호 (통권 제50호)
발행연도
수록면
604 - 610 (7page)
오류 신고하기

피인용 0

지하철 역사 지하수를 이용한 에어와셔에 관한 연구
검색

    초록·키워드

    Busan subway transportation system has been established a key role in the society last 20 years. However many people are suffering from hot and humid environment at subway station and platform due to deteriorated ventilation system as well as insufficient air conditioning system in existing stations and platforms. As a result, these systems require revitalization. There is about 5400tons of low temperature underground water is generated from subway stations every day. By using this method and air washer we are trying to lower the temperature. Air washer is commonly used for removing humidity but in this experiment it will be used as air precooling. This research offers result of experiment using air washer system to lower the temperature in large spaces like subway station. The experiment result has shown when L/G was the same, at condition which water spray temperature at 18℃ resulting inlet and outlet temperature difference larger. Also, in the same water spray temperature conditions, larger L/G condition showed a greater temperature difference. LCC evaluation of both system were shown that air washer system of using underground water will save 53% of the initial cost than refrigeration system, and save 75% of operating cost.

    최근 본 자료 전체보기

      UCI(KEPA) : I410-ECN-0101-2012-529-004138782