번역 버튼을 눌러보세요!
Application of US-NRC Multiple Spurious Operation Requirement in the Fire Protection of APR1400DC APR1400DC 원전의 미국 신규 화재방호 규제요건 다중오동작 적용 방안
논문 기본 정보
- 저자정보
- 발행연도
- 2013.11
- 수록면
- 190 - 190 (1page)
Application of US-NRC Multiple Spurious Operation Requirement in the Fire Protection of APR1400DC
초록·키워드
This paper mainly describes a regulatory framework of APR1400DC nuclear power plant design for fire-induced Multiple Spurious Operations(MSO). The APR1400 is to be certified by the US-Nuclear Regulatory Commission(US-NRC). The regulations and guidance provided for MSO by the NRC were basis for this paper. US-NRC document SECY-90-016, Section Ⅱ.D states "The ALWR(advanced light water reactor) Requirement Document indicates that fire protection will be as specified in 10 CFR 50.48 and Appendix R." SECY-90-016 also states that "current NRC guidance must be enhanced" and provides a list of those enhancement. Neither of SECY documents addresses the subject of MSO specifically. It is therefore believed that MSO requirements for APR1400 will be the same as for present operation plants. For application of the regulations and guidance, US-NRC RG 1.189, Rev.2 provides the current position for fire protection in nuclear power plant. Section C.5.3.1.1 of RG 1.189 endorses the use of Chapter 4 of NEI 00-01 as an acceptable approach to addressing MSO. Revision 3 of NEI 00-01, "Guidance for Post Fire Safe Shutdow ... 전체 초록 보기
본문·목차
인공지능 문자 인식 모델을 통해 추출된 텍스트로, 일부 오타나 오류가 포함될 수 있으나 지속적으로 개선 중입니다.
오류를 발견하셨다면 해당 부분을 드래그한 후 ' 를 통해 신고해주세요.
오류를 발견하셨다면 해당 부분을 드래그한 후 ' 를 통해 신고해주세요.
최근 본 자료 전체보기
UCI(KEPA) : I410-ECN-0101-2015-570-001313428