Heat transfer characteristics of a heat exchanger for low temperature waste heat recovery using oscillating capillary tube heat pipe(OCHP) were evaluated against the charging ratio variation of working fluid and various working fluids. R-142b, R-22 and R-290 were used as working fluids. The heat exchanger was composed of heat pipe with capillary tube bundles, having a 2.6 ㎜ in outside diameter, 1.4 ㎜ in inside diameter with 101 m length and 140 turns. Charging ratio of working fluid was 40% and 50%. Water was used as secondary fluid. Inlet temperature and mass velocity for each secondary fluid were 297 K, 280 K and 9~27 ㎏/㎡s, respectively. From experimental results, it was found that heat transfer performance of R-22 was higher than those of R-142b and R-290 and it was proportional to Figure of Merit for thermosyphon. As a result, it was thought that R-22 was the most reasonable working fluid of waste heat recovery for low temperature waste heat recovery.

목차

Abstract

1. Introduction

2. Operation principle and conventional studies for OCHP

3. Experimental apparatus and methods

4. Experimental results and consideration

5. Conclusions