An experimental study was performed to examine the heat transfer performance of individual rows of fin-tube heat exchangers. The heat transfer performance was measured using air-enthalpy type calorimeter. The examined heat exchangers consists of 7φ tube and fin patterns of them are slit and louver types. Equivalent fin spacing are 18 FPI for all samples, and the number of tube rows were 2. In order to evaluate the effects of fin-separation, one sample was physically separated between two rows while the other was connected. The tested air velocity varied from 0.7 to 2.5 ㎧ with 0.3 ㎧ interval. Heat transfer for each row are evaluated. It was observed that the heat transfer coefficient of the 2nd row were smaller than that of the 1st row at low Reynolds number while larger at high Reynolds number.