In recent years there has been an increasing Interest of the use of non-azeotropic binary mixtures to improve performance In heat pump systems, and to restrict the consumption of chlorofluorocarbon refrigerants.
In this study, in order to examine the performance and the systematizing the heat pump cycle characteristics for non-azeotropic refrigerant systems which are technically important halogenated refrigerant mixtures, the cycle characteristics on heat pump for pure R-22, R-114 and their mixtures were experimentally investigated.
The results show that cooling capacity for the mixtures significantly Increased at the evaporating temperature 5℃. The C.O.P of the 50wt% mixtures was considerably larger than for pure R-22, and compression power of the 25wt% was as much as 60% lower than the pure R-22. And even small fraction of a mixtures can lead to significant changes In the characteristics of heat pump cycle. This verified the importance of efficient weight fractions of mixtures.