This research investigates airtightness of the house and the individual rooms in newly-built apartment house, and performs field measure of supply and return air flow rate under the various operating conditions of several ventilation systems. The experiment is carried out to provide the relationship between the performancesof ventilation systems with airtightness of apartment house.
The results can be summarized as follows. 1) Similar natural ventilation rate is measured between 0.19 and 0.22 cycle/hour within apartment house. Average infiltration rate is measured as 38.4 CMH and its corresponding ventilation rate is about 0.2 cycle/hour. 2) The individual operation of ventilation systems decreases the system performance as 3 to 4 % in comparison with simultaneous operation of the systems, however the air velocity is not significantly changed.