An experimental investigation was carried out to examine the evaporative heat transfer characteristics in the double pipe heat exchanger using R-410a. The double pipe heat exchanger was helical coil type. The inner tube of double pipe heat exchanger was two types, spiral and circle. The experimental runs were carried out at a saturation temperature of refrigerant ranging between 5℃ and 15℃, and mass fluxes are 103.3~258.2 ㎏/㎡s. The inlet temperature of the water in the test section were 9℃, 12℃, 19℃ and 22℃. Heat transfer coefficient of refrigerant side of spiral type and circle type were 3.36~4.66 ㎾/㎡℃ and 2.64~3.86 ㎾/㎡℃. The pressure drop of refrigerant side for circle type was higher than that of spiral type at same mass flux. The effectiveness of spiral type and circle type were 0.34~0.66 and 0.19~0.57.