    A long term passive cooling system is considered as the most important safety feature for the nuclear design after the Fukushima Daiichi nuclear power plant accident in 2011. The conventional active pump driven safety systems are not available during a station Black Out (SBO) accident. The current design requirement on cooling time of the Passive Auxiliarly Feedwater System (PAFS) is about 8 hours only. To meet the 72 hours cooling time, the pool capacity of cooling water tank should be increased as much as 3~4 times larger than that of current water cooling tank. In order to extend the cooling time for 72 hours, a new passive air-water combined cooling system is proposed. This paper provides the feasibility of the combined passive air-water cooling system. The current pool capacity of water cooling system is preserved, and the cooling capability is extended by an additional air cooler.