    The simultaneous provision of cooling, heating and hot water in residential buildings has propelled the demand of cascade multi-functional heat pumps in recent times. There is however insufficient literature outlining the effect of temperature variations for cascade multi-functional heat pumps. The performance characteristics of water-to-water cascade multi-functional heat pump in heating-hot water mode was analyzed in this experimental study with emphasis on the variation of outdoor entering water temperature. Capacity of heating cycle increased greatly as outdoor entering water temperature increased. The hot water capacity also increased as OD EWT increased. Overall system COP increased up to 27.4% as OD EWT increased by 15℃.