This paper presents research results on the use of a corona detector and a pulse counter in order to diagnose for oil transformers.
Using these experimental apparatus, tests were carried out on a typical transformer oil containing different carbonized paper and various moisture contents to measure the picocoulomb values and pulse count.
Through the result of this study it was found that the picocoulomb values and pulse count of corona were depended on the getting stained in transformer oil.
The amplitude of the partial discharge amount and the number of pulse were decreased up to 70〔℃〕and then was increased as the oil temperature goes up.
It was concluded that the determination level for diagnosis of oil transformer was taken into account the temperature of transformer oil.
The use of pulse counter method, which have been taken the same property of voltage and temperature variation for the corona measurement method, considerably increase insulator availability.